Reduced Pressure
Principle Assembly.
The only assembly the State of Wisconsin allows between potable water and a high-hazard cross-connection. Two checks. A vented intermediate zone held below supply pressure. If the relief vent opens, something has gone wrong, and that something is now on the floor and not in the city's water main.
Construction
A Reduced Pressure Principle Assembly contains, in series along its main flow path: an inlet shutoff valve (SOV-1), a first check valve (CK-1), a differential pressure relief valve (RV) opening to atmosphere, a second check valve (CK-2), and an outlet shutoff valve (SOV-2). Four test cocks (TC-1 through TC-4) are drilled into the body at locations that let a tester read the pressure at the inlet, at the upstream side of CK-2, at the relief vent, and at the downstream side of CK-2. The intermediate zone between CK-1 and CK-2 is mechanically biased to sit at least 2.0 psi below the inlet pressure; when supply pressure drops or downstream pressure rises, the relief vent opens and dumps the contents of that zone to atmosphere through an air-gap drain. The assembly is the only device the state allows on a high-hazard cross-connection because it is the only family that cannot be defeated by a single check failure — the relief vent is the third line of defense, and it is loud when it works.1
Test sequence (ASSE 5110, §5.4.3)
The ASSE 5110 standard prescribes a specific five-valve sequence for annual testing of an RP. We perform it in this order, on every test, on every assembly, with a Mid-West 845-5 differential gauge bearing a NIST-traceable calibration sticker dated within the last twelve months. The full sequence appears below; the public-facing version is in the test report we file the same day.
| Step | Action | Read | Acceptance |
|---|---|---|---|
| 1 | Close SOV-2. Bleed gauge to TC#2, TC#3. | p2 − p3 (relief vent Δp) | ≥ 2.0 psid |
| 2 | Open TC#4. Read CK-2 differential. | p2 − p4 | ≥ 1.0 psid, no leak |
| 3 | Close TC#4. Open TC#3, read. | p3 (relief opens) | opens at ≥ 2.0 psid |
| 4 | Verify CK-1 holds against simulated back-pressure. | p1 − p2 | ≥ 1.0 psid, tight |
| 5 | Reopen SOV-2. Verify no continuous discharge. | visual | no leak after stabilization |
Failure modes
The seven failure modes we record, in order of how often we see them on a typical Milwaukee account (data from our 2025 books, n = 2,950 tests):
- CK-2 fouled · 28%
Sediment, biofilm, or a flake of solder fouls the second check seat. Common on small irrigation or kitchen RPs that sit without flow for weeks. Rebuild kit usually resolves.
- Relief vent continuous discharge · 21%
The vent opens and stays open. Diaphragm pinhole or seat damage. Customer notices a puddle under the assembly. Rebuild diaphragm and seat.
- CK-1 weak · 18%
First check holds less than 1.0 psid. Spring fatigue, scaling, or thermal stress. Rebuild typically fixes; replacement if the body itself shows pitting.
- SOV-2 won't fully close · 11%
A ball valve seat is worn, usually from being used as a throttle. Doesn't fail the test directly but prevents step 1.
- TC#3 plugged · 9%
Calcium deposit in the third test cock. Clean, lubricate, occasionally replace.
- Body crack at brass-to-bronze joint · 7%
Freeze damage. The whole assembly is condemned. Almost always a non-heated mechanical room.
- Wrong assembly for hazard · 6%
A DC found protecting a high-hazard cross-connection. Cited and replaced with an RP per SPS 382.41(11).
USC FCCCHR-approved models we stock
| Mfr / Model | Sizes | USC list # | Rebuild kit in cabinet |
|---|---|---|---|
| Watts 909 | 1/2″ – 2″ | 09-115 | Yes — CK-1, CK-2, RV diaphragm |
| Watts 957 | 2.5″ – 10″ | 09-118 | Yes — large-body kit |
| Wilkins 375 | 3/4″ – 2″ | 09-090 | Yes |
| Wilkins 375A | 2.5″ – 10″ | 09-091 | Partial — special-order body kits |
| Apollo 4ALF-500 | 1/2″ – 2″ | 09-128 | Yes |
| Conbraco 40-200 | 3/4″ – 2″ | 09-076 | Yes |
| Febco 825Y / 825YD | 3/4″ – 2″ | 09-103 | Yes |
| Febco 860 | 2.5″ – 10″ | 09-104 | Partial — special-order body kits |
Install rules per SPS 382.41(11)
Wisconsin's plumbing code sets installation rules that override manufacturer recommendations when they conflict. The ones we cite most often:
- Above grade
RPs may not be installed in pits or vaults. Their relief discharge must be visible and drain to a floor sink, hub drain, or air-gap drain — not to a sealed line.
- Minimum 12 inches above the flood-rim
The bottom of the assembly must be at least 12″ above the highest expected flood plane in the room.
- Clearance for testing
12″ minimum clearance below; 6″ on each side. We will not test an assembly that's been buried behind shelving — we will move the shelving or charge to.
- Freeze protection
In an unconditioned mechanical room, a heat tape and insulation jacket are required. In Milwaukee, "unconditioned" includes most parking-garage utility rooms.
- Identification tag
A metal or laminated tag with the assembly's serial number, install date, last test date, and protected hazard. We supply ours engraved on aluminum on installs and replacements.
Typical Milwaukee premises we install RPs on
The list below is the top ten premises types where we install or maintain an RP, in 2025 order. Numbers in parentheses are the share of our 2025 books:
- Restaurants and bars with beverage carbonators (24%)
- Dental clinics with vacuum (12%)
- K-12 chemistry classrooms (8%)
- Medical / urgent-care offices with autoclave (8%)
- Light industrial cooling-loop with glycol (7%)
- Veterinary clinics (5%)
- Commercial irrigation with fertigation (5%)
- Car washes (4%)
- Breweries (4%, including Lakefront's mash-tun fill line)
- Boiler feed at high-rise multifamily with glycol (3%)
Rebuild intervals
USC FCCCHR doesn't prescribe a calendar — they prescribe condition. Our internal calendar, refined from 11 years of Milwaukee water chemistry:
| Service | Typical rebuild interval | Notes |
|---|---|---|
| Indoor mechanical room, treated MWW water | 7–10 years | Most kitchen and dental installs |
| Foundry cooling-loop with glycol | 3–5 years | Glycol attacks EPDM diaphragms |
| Outdoor irrigation, freeze-cycled | 2–4 years | Thermal cycling fatigues springs |
| Carwash reclaim-system isolation | 2–3 years | Particulate-heavy |
| Dental vacuum isolation | 4–6 years | Amalgam particulate, mercury alloy |
References
- ASSE International. ASSE 1013 — Performance Requirements for Reduced Pressure Principle Backflow Preventers. asse-plumbing.org/standards
- USC Foundation for Cross-Connection Control and Hydraulic Research, Manual of Cross-Connection Control, 10th ed. usc.edu/dept/fccchr/manual.html
- Wisconsin DSPS, SPS 382.41 — Cross-connection control. docs.legis.wisconsin.gov
- Milwaukee Water Works, Cross-Connection Control Section §295-1. water.milwaukee.gov
- Watts Water Technologies, 909 Series technical specification. watts.com/products/909
- Mid-West Instrument, Model 845-5 Backflow Test Gauge. midwestinstrument.com