Walker's Point
Cross-Connection Co.
Test Cycle Q2 · 2026
425 W. Florida St., Mke 53204
WI DSPS CCCT-2118 · Q1 closed 31 Mar 2026 · Q2 in cycle — due 30 Jun 2026 · Q3 opens 01 Jul 2026 · Q4 closes 31 Dec 2026 · MWW §295-1 compliant · USC FCCCHR Listed
Assembly · Type DC · ASSE 1015 / CSA B64.5

Double Check
Valve Assembly.

Two checks in series. No vented intermediate zone. The moderate-hazard family — appropriate for cross-connections where a failure would be aesthetically unwelcome but not toxic. Office heating loops, multifamily makeup water, fire service without antifreeze.

Construction

A Double Check Valve Assembly is a Reduced Pressure assembly with the relief vent omitted. Two independent spring-loaded check valves sit in series along a single bronze or brass body, each with its own test cock immediately upstream. Inlet and outlet shutoffs frame the assembly. Three test cocks (TC-1, TC-2, TC-3) are accessed during the annual test. The two checks are independent and identical — neither relies on the other for sealing. Because there is no vented intermediate zone, a DC is sealed and may be installed in a vault or below grade where local code allows, though Milwaukee Water Works prefers above-grade installation for serviceability.1

Potable → SOV-1 CK-1 CK-2 SOV-2 → Premises TC#1 TC#2 TC#3 Double Check Valve Assembly — Type DC — three test cocks
Plate 04 · DC-1. Two checks in series. No relief vent. Three test cocks.

When a DC is right

Wisconsin's plumbing code allows a DC only where the protected cross-connection has been classified moderate hazard — a nuisance, an aesthetic problem, or a non-toxic chemistry. The protected systems we see most often on DCs in Milwaukee:

  • Sealed hydronic heating loop (no glycol)

    A sealed boiler-and-radiator system where the only makeup water is plain potable. Most Milwaukee mid-rise office buildings and brick four-flat hot-water systems.

  • Domestic-water booster pump

    A premises with a booster pump where the city's PSI runs low — common in West Allis blocks east of 70th Street. The booster is the moderate hazard.

  • Tankless water heater feeds

    Sealed instantaneous heaters with no chemical treatment.

  • Fire service without antifreeze, wet pipe

    A sprinkler system with no glycol, no foam, no chemicals — stagnant potable water under pressure. Use a DCDA (detector variant) for the meter requirement.

  • Cooling-tower makeup with no chem injection

    Rare but it happens. Most cooling towers are dosed with biocides and are high-hazard; if the dosing is downstream of the assembly and the assembly is on city-supplied makeup, a DC is allowed.

When a DC is wrong

We see four scenarios more than any others where a DC was specified but an RP is required:

  1. Boiler dosed with glycol. A DC on a glycol-treated boiler-loop makeup is non-compliant per SPS 382.41(11) table 41 since 2002, but we still find dozens of them on mid-century commercial blocks where the loop chemistry was added after the install.
  2. Restaurant carbonator. Soda-fountain carbonators are high-hazard back-pressure scenarios — CO₂ presses citric acid back through the copper supply line. Always RP. We replace 20+ of these per year on restaurant accounts where the prior assembly was a DC.
  3. Irrigation with fertigation. Any irrigation system with an injection pump (fertilizer, pesticide, surfactant) is high-hazard. Pre-2005 commercial irrigation in Milwaukee often used a DC; the 2005 SPS revision tightened the rule.
  4. Carwash reclaim isolation. Reclaim loops handle hydrocarbon-laden water. Always RP.

Test sequence (ASSE 5110, §5.5)

StepActionReadAcceptance
1Close SOV-2. Hose gauge to TC#2 / TC#3.p2 − p3 (CK-2 differential)≥ 1.0 psid, tight
2Bleed gauge to TC#1 / TC#2.p1 − p2 (CK-1 differential)≥ 1.0 psid, tight
3Reopen SOV-2. Verify no leak.visualno continuous discharge

Failure modes

From our 2025 books, the seven most common failure modes on DCs (n = 884 tests):

  • CK-2 weak · 31%

    Downstream check fatigues first; it sees the most thermal cycling.

  • CK-1 weak · 23%

    Upstream check; usually a contemporary failure with CK-2 in old installs.

  • Both checks weak · 12%

    Time for a rebuild on both ends. We do both even when only one fails.

  • TC plugged · 11%

    Calcium or solder flake.

  • SOV worn · 9%

    Won't fully close; the assembly cannot be tested.

  • Body crack from freeze · 8%

    Replacement.

  • Wrong assembly for hazard · 6%

    DC found where RP required.

USC FCCCHR-approved DC models we stock

Mfr / ModelSizesUSC list #
Watts 007 / 009 / 9191/2″ – 2″11-046
Watts 709 / 7572.5″ – 10″11-048
Wilkins 350 / 350A3/4″ – 10″11-035
Apollo 4A-1003/4″ – 2″11-058
Febco 850 / 805Y3/4″ – 2″11-061
Conbraco 40-1001/2″ – 2″11-022
Hersey FDC2.5″ – 10″11-014

Install rules per SPS 382.41(11)

DC-specific items, in addition to the general install rules in the SPS chapter:

  • Above-grade preferred but not required.

    Pit-installs are allowed for DC where space and freeze protection are otherwise impossible. Milwaukee Water Works prefers above-grade for ease of annual testing.

  • Identification tag with hazard class.

    Tag must say "moderate hazard" on a DC. If the assembly were ever to protect a high-hazard cross-connection, the tag becomes a citation.

  • Test clearance.

    6″ around the body. We need access to all three test cocks at once.

"The most common compliance failure in Milwaukee isn't a missed test — it's a DC where an RP should be. Always check what's downstream before you sign." — Okafor, 2024 MATC continuing-ed talk

References

  1. ASSE International, ASSE 1015 — DCV Assemblies. asse-plumbing.org
  2. Wisconsin DSPS, SPS 382.41 Table 41. docs.legis.wisconsin.gov
  3. USC FCCCHR Manual §11 (DC-rated assemblies). usc.edu/dept/fccchr
  4. MWW §295-1. water.milwaukee.gov
  5. Watts Water Technologies 007 series. watts.com